National Building Code of the Philippines

PD 1096 · 1977 · Building and construction law

Source checked. The source check identifies the document; it does not verify every transcribed word or its current legal effect. Recovered or scanned text may contain errors. Compare the wording and subsequent history with the linked legal source.

TEXT SEGMENT 18 / 27
(9) Fire pumps . Fire pumps shall have a capacity of not less than 1,000 liters per minute with a pressure of not less than 2 kilograms per sq. cm. at the topmost hose outlet. The source of supply for such pump shall be a street water main of not less than 100 mm, diameter or a well or cistern containing a one-hour supply. Such pumps shall be supplied with an adequate source of power and shall be automatic in operation. (10) Hose and Hose Reels . Each hose outlet of all interior wet standpipe shall be supplied with a hose not less than 38 millimeters in diameter. Such hose shall be equipped with a suitable brass or bronze nozzle and shall be not over 23.00 meters in length. An approved standard form of wall hose reel or rack shall be provided for the hose and shall be located so as to make the hose readily accessible at all times and shall be recessed in the walls or protected by suitable cabinets. (d) Basement Pipe Inlets . Basement pipe inlets shall be installed in the first floor of every store, warehouse, or factory where there are cellars or basements under same: Except, wherein such cellars or basements there is installed a fire-extinguishing system as specified in this Code or where such cellars or basement are used for banking purposes, safe deposit vaults, or similar uses. (1) Material . All basement pipe inlets shall be of cast iron, steel, brass, or bronze with lids of cast brass or bronze and shall consist of a sleeve not less than 200 millimeters in diameter through the floor extending to and flush with the ceiling below and with a top flange, recessed with an inside shoulder, to receive the lid and flush with the finished floor surface. The lid shall be a solid casting and shall have a ring lift recessed on the top thereof, so as to flushed. The lid shall have the words "FOR FIRE DEPARTMENT ONLY, DO NOT COVER UP" cast on the top thereof. The lid shall be installed in such a manner as to permit its removal readily from the inlet. (2) Location . Basement pipe inlets shall be strategically located and kept readily accessible at all times to the Fire Department. (e) Approval . All fire-extinguishing systems, including automatic sprinklers, wet and dry standpipes, automatic chemical extinguishers, basement pipe inlets, and the appurtenances thereto shall meet the approval of the fire Department as to installation and location and shall be subject to such periodic test as it may require. SECTION 1213. Stages and Platform. (a) Stage Ventilators . There shall be one or more ventilators constructed of metal or other incombustible material near the center and above the highest part of any working stage raised above the stage roof and having a total ventilation area equal to at least five percent of the floor area within the stage walls. The entire equipment shall conform to the following requirements: (1) Opening Action . Ventilators shall open by spring action or force of gravity sufficient to overcome the effects of neglect, rust, dirt, or expansion by heat or wrapping of the framework. (2) Glass . Glass, if used in ventilators must be protected against falling on the stage. A wire screen, if used under the glass, must be so placed that if clogged it cannot reduce the required ventilating area or interfere with the operating mechanism or obstruct the distribution of water from the automatic fire extinguishing systems. (3) Design . Ventilators, penthouses, and supporting framework shall be designed in accordance with this Code. (4) Spring Actuation . Springs, when employed to actuate ventilator doors, shall be capable of maintaining full required tension indefinitely. Springs shall be no stressed more than fifty percent of their rated capacity and shall not be located directly in the air stream, nor exposed to elements. (5) Location of Fusible Links . A fusible link shall be placed in the cable control system on the underside of the ventilator at or above the roof line or as approved by the Building Official, and shall be so located as not to be affected by the operation of fire-extinguishing systems. (6) Control . Remote, manual, or electrical control shall provide for both opening and closing of the ventilator doors for periodic testing and shall be located at a point on the stage designated by the Building Official. When remote control of ventilator is electrical, power failure shall not affect its instant operation in the event of fire. Hand winches may be employed to facilitate operation of manually controlled ventilators. (b) Gridirons.– (1) Gridirons, fly galleries, and pin-rails shall be constructed of incombustible materials and fire protection of steel and iron may be omitted. Gridirons and fly galleries shall be designed to support a live load of not less than 367 kilograms per square meter. Each loft block well shall be designed to support 373 kilograms per linear meter and the head block well shall be designed to support the aggregate weight of all the loft block wells served. The head block well must be provided with an adequate strongback or lateral brace to offset torque. (2) The main counterweight sheave beam shall be designed to support a horizontal and vertical uniformly distributed live load sufficient to accommodate the weight imposed by the total number of loft blocks in the gridiron. The sheave blocks shall be designed to accommodate the maximum load for the loft or head blocks served with a safety factor of five. (c) Rooms Accessory to Stage . In a building having a stage, the dressing room sections, workshops, and store rooms shall be located on the stage side of the proscenium wall and shall be separated from each other and from the stage by not less than a One-hour Fire Resistive Occupancy Separation. (d) Proscenium Walls . A stage shall be completely separated from the auditorium by a proscenium wall or not less than two-hour incombustible construction. The proscenium wall shall extend not less than 1.20 meters above the roof over the auditorium. Proscenium walls may have the addition to the main proscenium openings, one opening at the orchestra pit level and not more than two openings at the stage floor level, each of which shall be not more than 2.00 square meters in area. All openings in the proscenium walls of stage shall be protected by a fire assembly having a one and one-half fire-resistive rating. The proscenium opening, which shall be the main opening for viewing performances, shall be provided with a self closing fire-resistive curtain as specified in this Code. (e) Stage Floor . The type of construction for storage floors shall depend upon the requirements based on the type of Occupancy and the corresponding fire-resistive requirements. All parts of the stage floor shall be designed to support not less than 620 kilograms per square meters. Openings through stage floor shall be equipped with tight-fitting trap doors of wood of not less than 5 millimeters nominal thickness. (f) Platforms . The type of construction for platforms shall depend upon the requirements based on the type of Occupancy and corresponding fire-resistive requirements. Enclosed platforms shall be provided with one or more ventilators conforming to the requirements of stage ventilators: Except, that the total area shall be equal to five percent of the area of the platform. When more than one ventilator is provided, they shall be so spaced as to provide proper exhaust ventilation. Ventilators shall not be required for enclosed platform having a floor area of 45.00 square meters or less.